TO: Mayor and City Commission
FROM: Cale Curtis, City Manager
DATE: December 2, 2026
Title
A RESOLUTION OF THE CITY OF THE CITY OF MARGATE, FLORIDA, SELECTING ION EXCHANGE FOR THE CITY’S PFAS TREATMENT METHOD; APPROVING ONTERRIS, INC. AS THE SOLE-SOURCE PROVIDER OF THE SPECIFIED PROPRIETARY PFAS ION EXCHANGE TREATMENT EQUIPMENT AND MEDIA, WITH MTS ENVIRONMENTAL AS ITS AUTHORIZED FLORIDA DISTRIBUTOR, SUBJECT TO A WRITTEN PROCUREMENT DETERMINATION; APPROVING A DIRECT PURCHASE FROM ONTERRIS, INC. AT A NOT-TO-EXCEED PRICE OF $5,995,931.00; AUTHORIZING EXECUTION OF RELATED PURCHASE DOCUMENTS; PROVIDING FOR IMPLEMENTATION AND AN EFFECTIVE DATE.
BACKGROUND:
The City of Margate owns and operates a drinking water treatment plant and is working to remove several per- and polyfluoroalkyl substances (PFAS), a group of chemicals often called “forever chemicals,” from its drinking water.
On April 10, 2024, the U.S. Environmental Protection Agency (EPA) adopted federal drinking water standards for several PFAS, including perfluorooctanoic acid (PFOA) and perfluorooctane sulfonic acid (PFOS). Under the current rule, public water systems must meet the applicable standards by April 26, 2029. Compliance means that running annual average of four quarterly samples is at or below 4 ppt. To allow time to collect the four quarterly samples and make any needed adjustments, DEES must have the treatment system constructed and operating by March 2028.
Finished-water samples collected from our plant from April 2025 through February 2026 showed average concentrations of 7.5 parts per trillion (ppt) of PFOA and 24.6 ppt of PFOS. Both averages exceed the federal limit of 4 ppt for each compound. These are separate averages for PFOA and PFOS, not a combined “total PFAS” concentration.
In 2025, the Department of Environmental and Engineering Services (DEES) retained consultant Hazen and Sawyer to evaluate PFAS treatment options and conduct pilot testing at the City’s Water Treatment Plant. In its October 2026 evaluation, Hazen and Sawyer concluded that the City’s existing lime softening process alone cannot remove PFOA and PFOS to the levels required by the EPA PFAS Rule. Additional treatment is needed to achieve compliance while meeting the City’s projected 2045 maximum day demand of 7.1 million gallons per day (MGD). Based on an evaluation of the combined performance and cost of various treatment methods, Hazen and Sawyer has identified Ion Exchange as the preferred baseline treatment alternative.
DEES staff considers Onterris a strong option because of their proven 10-year track record of 350 PFAS treatment systems nationwide, with projects in Georgia, New Jersey, and Pennsylvania, and more than 17 billion gallons of PFAS-impacted water treated; because this technology handles a broad range of contaminants, including PFAS, TOC (Total Organic Carbon ), VOC’s (Volatile Organic Compounds), metals, nitrates, and pharmaceuticals; because their proposal includes an onsite pilot to evaluate the appropriate media prior to final media selection; because the system is sized for the City’s 8 MGD design flow; because this equipment is American-designed and American-made; and because the manufacturer of this system is not an original creator or contributor of PFAS chemicals, as in the case of DuPont and 3M whose membranes are a common treatment method.
At the former Pease Air Force Base in Portsmouth, New Hampshire, Onterris’ case materials describe a regenerable Ion Exchange system used to protect off-site drinking water. The materials report that the system treated more than 75 million gallons, with PFOA and PFOS consistently non-detected in the treated water. This U.S. field experience with regenerable Ion Exchange supports DEES staff’s recommendation to pilot the proposed system using Margate’s water.
Onterris’ proposal is for furnishing a modular H Series Ion Exchange system, including the Ion Exchange equipment, onsite media optimization pilot, initial media, startup and commissioning support, with final selection between SORBIX PURE and RePURE media subject to pilot and design review. Onterris’s proposal lists an equipment total cost of $5,995,931, including a $700,000 Customer Change Allowance and $147,400 in estimated freight.
MTS Environmental’s letter identifies Onterris as the exclusive U.S. source for the specified equipment and media. The regenerable RePURE resin is designed for reuse, which would reduce spent media waste and operating costs over other treatment alternatives. Onterris also reports that EPA Administrator Lee Zeldin visited its Portland, Maine office, where the company presented PFAS treatment solutions targeted to serve small and rural communities as well as larger utilities.
Hazen and Sawyer’s preliminary estimate for the baseline Ion Exchange project starts at approximately $17.7 million. This price tag could increase to $26.4 million or more if additional treatment units are needed for taste, color, odor, or TOC removal. The Department plans to evaluate those treatment needs as a possible Phase 2. Onterris’ equipment and initial media are priced at approximately $6 million. Installation by the City’s existing design-builder under a separate contract is preliminarily estimated at approximately $8 million, for a current project estimate of about $14 million-approximately $3.7 million below Hazen and Sawyer’s lowest estimate, before any Phase 2 work and subject to final design and cost confirmation.
RECOMMENDATION: Approval
FISCAL IMPACT: $5,995,931.00
Bond 464.9090.565001 - Project 6056, “WTP Improvements”
CONTACT PERSON: Curt Keyser, DEES Director